• Inicio
  • Comprobador de pérdidas dieléctricas de transformadores IPF Comprobador Tan Delta de transformadores

Comprobador de pérdidas dieléctricas de transformadores IPF Comprobador Tan Delta de transformadores

Breve descripción:

ARTÍCULO: RUN-ZC8860

Transformer capacitance and tan delta tester is used for on-site anti-interference dielectric loss measurement, or precision dielectric loss measurement in the laboratory. The instrument is an integrated structure with built-in dielectric loss bridge, variable frequency power supply, test transformer and standard capacitors. Using frequency conversion anti-interference and Fourier transform digital filtering technology, automatic and intelligent measurement, the measurement data is very stable under strong interference.

Service: The instrument will be repaired and replaced free of charge for product quality problems within one year from the date of purchase, and will provide lifetime warranty and technical services. If you find any abnormalities or malfunctions in the instrument, please contact the company in time to arrange the most convenient solution for you.

  • Run Test Electric Facebook logo
  • Run Test Electric LinkedIn logo

Detalle del producto

Etiquetas del producto

Ⅰ:Breve Introducción sobre el probador de pérdida dieléctrica del transformador:

RUN-ZC8860 Capacidad del transformador y probador tan delta is used for on-site anti-interference dielectric loss measurement, or precision dielectric loss measurement in the laboratory. The instrument is an integrated structure with built-in dielectric loss bridge, variable frequency power supply, test transformer and standard capacitors. Using frequency conversion anti-interference and Fourier transform digital filtering technology, automatic and intelligent measurement, the measurement data is very stable under strong interference. Besides functions listed above, Run-ZC8860 also has the function of insulation resistance measurement. The wiring method for measuring the insulation resistance is exactly the same as that of the dielectric loss measurement. The dielectric loss and the insulation resistance can be measured in one connection which significant improve test speed and reduce burden of test.

Ⅱ:Technical Parameters of the Transformer Tan Delta Tester:

Precisión Cx: ±(reading×1%+1pF) Tgδ: ±(reading×1%+0.00040)
Antiinterferencias Frecuencia variable antiinterferencias, la precisión anterior puede alcanzarse incluso bajo interferencias 200%.
Gama de capacitancias Internal HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV External HV: 3pF~1.5μF/10kV 60pF~30μF/0.5kV Best Resolution: 0.001pF, 4 valid digits.
tgδ range Resolución ilimitada, 0,001%, identificación automática para capacitancia, inductancia y resistencia de tres artículos probados.
Rango de corriente de prueba 5μA~5A
Alta tensión interna Set voltage range: 0.5~10kV Maximum output current: 200mA
Frecuencia de prueba 40~70Hz integer frequency 50/60 Hz, 60/70Hz automatic dual variable frequency Frequency accuracy: ±0.01Hz
Alta tensión externa UST, maximum test current is 5A/ 40~70Hz GST, maximum test current is 10kV/5A/40-70Hz
Salida de baja tensión de autoexcitación CVT Tensión de salida 3~50V, corriente de salida 3~30A
Medir la duración Alrededor de 40s, varía según el método de medición
Alimentación de entrada 220 VAC, 50Hz , alimentado por corriente alterna o generador
Interfaz de ordenador Interfaz RS232 estándar
Impresora Microimpresora integrada
Temperatura de funcionamiento -10℃~50℃
Humedad relativa <90%, Sin condensación
Dimensiones generales 460×360×350 mm
Peso 28 kg

Ⅲ: Detailed pictures about the Transformer Capacitance&Dissipation Factor Test:

 

Ⅳ: Features oh the IPF Transformer Dielectric Loss Tester:

1. The instrument uses Fourier transform digital filtering technology to measure capacitance, dielectric loss and other parameters. The test result has high precision and is easy to realize automatic measurement. 2. The instrument adopts frequency conversion technology to eliminate 50Hz power frequency interference in the field. Even in the environment of strong electromagnetic interference, reliable data can be measured. 3. It is easy to operate with full touch LCD. Full touch LCD screen, super full graphics operation interface, each process is very clear, operators can use without additional professional training. The whole process can be measured by touch. 4. Storage data: It is equipped with a calendar chip and a large-capacity memory, which can save the test results at any time, view the historical records at any time, and print out. The current time and storage time can be displayed and printed at any time. 5. Scientific and advanced data management: Instrument data can be exported through U disk, and can be viewed and managed on any PC by special software. 6. The instrument is easy to operate and the measurement process is controlled by microprocessor. As long as the appropriate measurement mode is selected, the measurement of data can be completed automatically under the control of microprocessor. 7. Integrated model, with standard capacitor and high voltage power supply, is convenient for field test and reduces field wiring. 8. The instrument has high accuracy and can meet the requirements of oil dielectric loss measurement. Therefore, only standard oil cup and special testing line are needed to realize oil dielectric loss measurement. 9. It has the function of low voltage shielding for reverse wiring. Under the condition of 220 kV CVT bus grounding, it can measure the dielectric loss of 110 kV reverse wiring without disconnection. 10. Can do AC voltage withstand test. It is convenient for PT and CT to do AC voltage withstanding test twice and 400V low voltage system to do voltage withstanding test. 11. It can identify the frequency of external high-voltage power supply from 40Hz to 70Hz, and allow large capacity and high voltage dielectric loss test with power frequency power supply or series resonant power supply. 12. It has the function of CVT test and can realize the self-excitation test of CVT. It can set four protection restrictions of high voltage/current and low voltage/current to ensure the safety of person and equipment. 13. When testing CVT, not only the capacitance and dielectric loss values of C1 and C2 can be automatically tested, but also the total capacitance and dielectric loss values of CVT equipment can be tested. 14. With a thermal printer, it can print out, with a calendar clock, to facilitate users to produce test reports, with U disk output. 15. With computer interface. A computer can control 32 instruments, which can be integrated into an integrated high-voltage test vehicle to realize measurement, data processing and report output. 16. Grounding protection function. When the instrument is not grounded or grounded badly, the instrument does not enter the normal procedure and does not output high voltage. Overcurrent protection function, the instrument will not be damaged when the sample is short-circuit or breakdown. 17. Electric shock protection function. When the instrument operator accidentally electric shock, the instrument will immediately cut off the high voltage to ensure the safety of the test personnel.

 