Deixe a sua mensagem

           
10A 3 Channels Transformer Winding Resistance Tester - Run Test
  • Início
  • 10A 3 Channels Transformer Winding Resistance Tester

10A 3 Channels Transformer Winding Resistance Tester

Breve descrição:

ITEM: RUN-DCR310AS CURRENT: 10A The winding resistance tester has the functions of three-phase simultaneous power-on, independent current and voltage sampling, simultaneous measurement and display of three-phase resistance and three-phase unbalance rate, so as to greatly shorten the test period of transformer DC resistance and solve the problems about long time consumption for DC resistance measurement of each tap winding in power transformers. SERVICE:  The instrument will be repaired and replaced free of charge for product quality problems within one year from the date of purchase, and will provide lifetime warranty and technical services. If you find any abnormalities or malfunctions in the instrument, please contact the company in time to arrange the most convenient solution for you.
  • Logótipo do Facebook da Run Test Electric
  • Logótipo do LinkedIn da Run Test Electric

Detalhe do produto

Etiquetas de produtos

Video of this transformer winding resistance tester

Ⅰ: Overview about the 10A Aparelho de teste de resistência de enrolamento trifásico:

Este equipamento de teste tem função de teste simultâneo trifásico, função de aumento magnético e função de desmagnetização. 
O testador de resistência de enrolamento tem as funções de ligação trifásica simultânea, amostragem independente da corrente e da tensão, medição e visualização simultâneas da resistência trifásica e da taxa de desequilíbrio trifásico, de modo a reduzir significativamente o período de teste da resistência CC do transformador e a resolver os problemas de consumo de tempo prolongado para a medição da resistência CC de cada enrolamento de derivação nos transformadores de potência.

Ⅱ: Especificações do aparelho de teste de resistência DC:


10A20A40A

AtualTrifásico5A+5A 1A+1A 200mA+200mA10A+10A 5A+5A 1A+1A20A+20A 10A+10A 5A+5A 1A+1A 200mA+200mA25A+25A 10A+10A 5A+5A 1A+1A 200mA+200mA
Monofásico10A/5A/1A/200mA/20mA20A/10A/5A/1A/200mA40A/20A/10A/5A/1A/200mA/20mA50A/20A/10A/5A/1A/200mA/20mA
GamaTrifásico5A+5A:2mΩ~1.2Ω 1A+1A:10mΩ~6Ω 200mA+200mA: 50mΩ~30Ω10A+10A:1mΩ~0.6Ω 5A+5A:2mΩ~1.2Ω 1A+1A:10mΩ~6Ω20A+20A:0.5mΩ~0.3Ω 10A+10A:1mΩ~0.6Ω 5A+5A:2mΩ~1.2Ω 1A+1A:10mΩ~6Ω 200mA+200mA:50mΩ~30Ω25A+25A:0.4mΩ~0.1Ω10A+10A:1mΩ~0.6Ω 5A+5A:2mΩ~1.2Ω 1A+1A:10mΩ~6Ω200mA+200mA:50mΩ~30Ω
Monofásico10A:1mΩ~2Ω 5A:2mΩ~4Ω 1A:10mΩ~20Ω 200mA:100mΩ~100Ω 20mA:10Ω~20KΩ20A:0.5mΩ~1Ω10A:1mΩ~2Ω 5A:2mΩ~4Ω 1A:10mΩ~20Ω200mA:100mΩ~100Ω40A:0.25mΩ~0.5Ω 20A:0.5mΩ~1Ω 10A:1mΩ~2Ω 5A:2mΩ~4Ω 1A:10mΩ~20Ω 200mA:100mΩ~100Ω 20mA:10Ω~20KΩ50A:0.20mΩ~0.3Ω 20A:0.5mΩ~1Ω 10A:1mΩ~2Ω 5A:2mΩ~4Ω 1A:10mΩ~20Ω 200mA:100mΩ~100Ω 20mA:10Ω~20KΩ
Exatidão±0,2%+2 dígitos
Melhor resolução0.1μΩ
Temperatura de funcionamento-10~40℃
Fonte de alimentaçãoAC220V±10%, 50Hz±1Hz
 

Ⅲ: Show detalhado Sobre o testador de resistência dc do transformador:

10A 3 Channels Transformer Winding Resistance Tester 10A 3 Channels Transformer Winding Resistance Tester 10A 3 Channels Transformer Winding Resistance Tester 10A 3 Channels Transformer Winding Resistance Tester

Ⅳ: Caraterísticas funcionais Sobre o teste de resistência DC:

1. For large transformers whose five-column core and low-voltage windings are connected in delta, the instrument can use the method of high and low-voltage series excitation for testing. The instrument automatically connects the magnetizing circuit of the windings, which can quickly and accurately test the DC resistance of the low-voltage windings. 
2. Ecrã tátil LCD de 7 polegadas de alta resolução, fácil de utilizar no local. Boa visibilidade mesmo sob luz forte. 
3. The instrument is equipped with three-phase test function, in order to complete the three-phase direct resistance measurement in one connection of the star-connected winding, and automatically calculate the three-phase unbalance rate, which greatly saves the measurement time and improves the work efficiency. The phase-by-phase test function can also be used to perform phase-by-phase tests on transformers with YN and D(Y) connections until the test is completed. 
4. Comprehensive protection circuit and sound discharge alarm, clear discharge indication. 
5. Easily set the test winding, tap position, phase, test temperature, converted temperature etc. 
6. Internal data storage up to 100 sets. 
7. RS232 port and USB Port for data storage and PC communication. 
8. Built-in high-speed micro printer.
  1. Ⅳ:  Medidas de segurança aquando da realização do teste:

    1) Must read this manual carefully before using the tester; 
  2. 2) The tester operator should understand the common knowledge on general electrical devices or instruments; 
  3. 3) The tester can be used indoors and outdoors, but it should be protected from rain, corrosive gas, excessive dust, and high temperature; 
  4. 4) The tester is a precision instrument and any severe vibration must be avoided;
  5. 5) The tester should be maintained, repaired and adjusted by professionals; 
  6. 6) After the test, be sure to wait for the discharge alarm to stop before turning off the power and removing the test wires; 
  7. 7) When measuring the no-load voltage-regulating transformer, the tap changer can be switched only after the discharge indication alarm stops.8) During the test, do not move the test clips and the power lines.

Ver o nosso  Testador de resistência DC for more information!!

Deixe a sua mensagem